I had an unusual task for Cameron to take care of and he performed it well and with good spirit. Charge was very reasonable.
We had a great experience with Comfort Central. The crew was professional and polite.
Cameron and the entire Comfort Central Team have been a godsend for all of our HVAC needs. Strongest recommendation!
The technician was knowledgeable and conscientious. He diagnosed the issue quickly and offered suggestions for further follow up.
We can always rely on Comfort Central to provide convenient and expert service followed with a detailed report on the condition of our HVAC equipment.
Cameron always arrives on time and performs his work efficiently.
They come when I call, they do good work, and they are courteous. What’s not to like?
Cameron did a great job, as he does every time! Highly recommend Comfort Central.
Thomas was very professional and on time.He was the informative and friendly
Delivery of front panel for Mitsubishi system
Could not do start up due underground electrical wire being shorted to neutral. Electricians gonna have to run a new high voltage wire to the panel inside the garage. However, we wired the outdoor unit and put a surge protector on it. Both outbuilding and garage are ready for start up once the power is corrected.
Performed heating tune up service on dual fuel system checking all electrical components, refrigerant balance, unit start up, operation, defrost, shutdown, cleaning and inspection of all furnace combustion components, treatment of drains, performed full combustion analysis on system. Everything looks and runs great!
Performed heating tune up service on heat pump system checking all electrical components, refrigerant balance, unit start up, operation, defrost, shutdown. Everything looks and run great!
Found system thermostat set to O/B on cool - remedied issue outdoor unit works normally again - found indoor blower not coming on - recommend replacement of indoor blower motor board. Will call with pricing and availability. Also wants a quote on surge protection
Performed heating tune up service on heat pump system checking all electrical components, refrigerant balance, unit start u, operation, shutdown, cleaning of indoor coil and treatment of drain, testing of defrost. Everything looks and runs great!
Performed heating tune up service on dual fuel system checking all electrical components, refrigerant balance, unit start up, operation, shutdown, defrost, performed full combustion analysis, treated drain lines, cleaned all furnace components. Everything looks and runs great!
Performed repair of blower motor control board and installation of outdoor surge protector. After completing repair and installation found system blower motor receiving full voltage from board 240v and 24v but blower motor not coming on. This indicates a failure of the blower motor. Recommend replacement of blower motor also.
Cleaned outdoor coils to complete cooling tune up service
SEER2 20; HSPF2 10; EER2 13 Make: Mitsubishi Model: MXZ-2D20NL Outdoor Unit (2) MSZ-GX09NL Indoor Units Installation shall include: Above listed equipment plus installation. • All work will be completed in a professional workmanlike manner. • This system will serve the basement. One indoor unit will go in the office, the other indoor unit will go in the bedroom. • We will install a Buck transformer and a surge protector on the outdoor unit to protect it from dirty power. • Line voltage electrical is included. • Mitsubishi Factory Warranty: Twelve (12) years all parts • One (1) Year Labor Warranty Provided by Comfort Central, Inc. • Ten (10) Year Guarantee on Comfort Central, Inc. Workmanship. • 100% Customer Satisfaction Guarantee for the first year.
Believe loss of air flow caused by outdoor vent filters being plugged - removed vent filters and cleaned them and cycled to check operation - adjusted master bathroom duct - cycled all bathroom fans to check operation - everything runs normally again.
Performed tune up service on minisplit systems checking all electrical components, refrigerant balance, unit start up, operation, shutdown. Found great room system low on refrigerant indicative of a refrigerant leak on system. Checked system over with halogen leak detector inspecting for leaks on both indoor and outdoor units and lineset between. Tightened flare nut and added 1 lb r410a to system and rechecked system for leaks. Did not indicate any leaks. Everything looks and runs great!
Condensation dripping from coil onto air handler through ductwork into garage Contacted Carrier to verify that this particular unit will work in a downflow. They informed me it would. The downflow kit was properly installed on the coil of the air handler. This is a2 1/2 ton system. It requires around 1000 CFM to work properly. I performed a static pressure test and verified that the system is .42 wc. We looked in the installation manual and found that at that pressure and where the blower was set. It was only 780 CFM. We just did the blower motor and brought it up to 985 CFM. By doing this, the system will have more air blowing across the coil Which will make the coil not as cold and hopefully not condensing as much water to prevent it from dripping off. At 780 CFM, the coil would be much colder condensing, more water, allowing it to drip. I’m not sure if making this adjustment actually fixed anything I would be surprised if it did. I would leave the fan in the on position until all t
Found evaporator coil leak on Bosch heat pump system causing unit not to operate correctly. Recommend replacement of evaporator coil. Will call with availability of warranty coil. Added7 pounds of 410 a. 110/224. 14sh. 10sc. 22° temperature difference